Primary voltage limit |
85...264 V
|
Network frequency |
50/60 Hz
|
Network frequency limits |
47…63 Hz
|
Apparent power |
0.07 kVA
|
Input current |
0.52 A 240 V 1.04 A 115 V
|
Inrush current |
30 A 120 V 60 A 240 V
|
I²t on activation |
1 A².s 120 V 3 A².s 240 V
|
It on activation |
0.05 A.s 120 V 0.07 A.s 240 V
|
Protection type |
Internal fuse not accessible for primary circuit Overload protection for secondary circuit Overvoltage protection for secondary circuit Short-circuit protection for secondary circuit
|
Current at secondary voltage |
0.9 A 24 V DC sensor power supply 1.3 A 24 V DC I/O module power supply and processor 4.5 A 3.3 V DC I/O module logic power supply
|
Maximum power dissipation in W |
8.5 W
|
Status LED |
1 LED (green)rack voltage OK: 1 LED (green)sensor voltage:
|
Control type |
RESET push-button cold restart
|
Electrical connection |
1 connector 2 pin(s)alarm relay 1 connector 5 pin(s)line supply, protective earth, 24 V DC input sensor
|
Insulation resistance |
>= 100 MOhm primary/ground >= 100 MOhm primary/secondary |